Res | Data | |||||
1 | Tensio aestimata | KV | 40.5 | |||
2 | Currens Aestimatus | A | ||||
3 | Currens interruptionis circuitus brevis aestimatus | KA | 20 | 25 | ||
4 | Currens brevis circuitus aestimatus (apicem) | 50 | 63 | |||
5 | Currens brevis (stabilis thermalis) aestimatus | 20 | 25 | |||
6 | Sustinentia apicis aestimata (stabilitas dynamica) cursus | 50 | 63 | |||
7 | Duratio circuitus brevis aestimata | S | 4 | |||
8 | Gradus insulationis aestimatus (1 min) | Tensio sustinenda frequentiae potentiae 1min | Siccus | KV | 95 | |
Humidus | 80 | |||||
Impulsus fulminis sustinere tensionem (apicem) | CLXXXV | |||||
9 | Ordo operandi aestimatus | Tempora | 20 | |||
10 | Tempora interruptionis currentis brevis circuitus aestimata | ms | ≤80 | |||
11 | Tempus plenum exstinctionis (cum mechanismo vernali) | -0.3S-CO- 180S-CO 0-0.3S-CO-180S-CO | ||||
12 | Vita mechanica | Decem milia | ||||
13 | Tensio operativa aestimata | AC110,220, DC110,220 | ||||
14 | Distantia aperitionis contactus | 20 | ||||
15 | Distantia contactus ultra tempus peragrationis | 5±1 | ||||
16 | Tempus resilitionis | ≤5 | ||||
17 | Resistentia continua per circuitum phasicum | ≤120 | ||||
18 | Interruptor CircuitusDimensiones (LxAxA) | 2460×2400×500 | ||||
19 | Pondus Totale cum Mechanismo | kg | 1100 |