IEC Electrica
Tensio AC Nominalis (50/60Hz) | 60V | 120V | 230V | 230V | ||
Maxima Tensio Operativa Continua (AC) | (LN) | Uc | 75V | 150V | 275V | 320V |
(N-PE) | Uc | 255V | 255V | 255V | 255V | |
Nomina Currens Exonerationis (8/20)μs) | (LN)/(N-PE) | In | 20 kA/25 KA | |||
Maxima Currens Exonerationis (8/20)μs) | (LN)/(N-PE) | lmaximum | 50kA/50KA | |||
Impulsus Fluxus Exonerationis (10/350)μs) | (LN)/(N-PE) | ldiabolus | 12.5 kA/25 KA | |||
Energia Specifica | (LN)/(N-PE) | W/R | 39kJ/Ω/625KJ/Ω | |||
Impetus | (LN)/(N-PE) | Q | 6As/12.5As | |||
Gradus Protectionis Tensionis | (LN)/(N-PE) | Up | 700V/1500V 1000V/1500V 1500V/1500V 1600V/1500V/ | |||
Sequere Aestimationem Interruptionis Currentis | (N-PE) | I | 100ARMS | |||
Tempus Responsionis | (LN)/(N-PE) | tA | <25 ns/<100ns | |||
Fusus Subsidiarius (max) | 315A/250A gG | |||||
Cursus Brevis Circuitus Aestimatio (AC) | (LN) | lscCR | 25kA/50kA | |||
TOV Resistere 5s | (LN) | UT | 114V | CLXXXV | 335V | 335V |
TOV 120 min. | (LN) | UT | 114V | 230V | 440V | 440V |
Modus | Resistere | Defectus Tutus | Defectus Tutus | Defectus Tutus | ||
TOV resistere 200s | (N-PE) | UT | 1200V | |||
Numerus Portuum | 1 |
UL Electrica
Maxima Tensio Operativa Continua (AC) | (LN)/(N-PE) | MCOV | 75V/255V | 150V/255V | 275V/255V | 320V/255V |
Aestimatio Protectionis Tensionis | (LN)/(N-PE) | VPR | 330V/1200V | 600V/1200V | 900V/1200V | 1200V/1200V |
Currens Emissionis Nominalis (8/20μs) | (LN)/(-PE) | In | 20KA/20KA | 20KA/20KA | 20KA/20KA | 20KA/20KA |
Cursus Brevis Circuitus Aestimatio (AC) | (LN) | SCCR | 200KA | 150KA | 150KA | 150KA |
Mechanica et Ambientalis
Ambitus Temperaturae Operativae | Ta | -40°F ad +158°F [-40°Celsiusad +70CelsiusI |
Humiditas Operativa Permissa | RH | 5%…95% |
Pressio atmosphaerica et altitudo | 80k Pa...106k Pa/-500m...2000m | |
Torques Cochleae Terminalis | Mmax | 39.9 lbf-in [4.5 Nm] |
Sectio Transversa Conductoris (max) | 2AWG (Solidum, Filum)/4AWG (Flexibile) | |
35mm²(Solidum, Filatum)/25 mm²(Flexibilis) | ||
Montatio | Ferrivia DIN 35 mm. EN 60715 | |
Gradus Protectionis | IP 20 (intus) | |
Materia Domus | Thermoplasticum: Gradus Extinctionis UL94V-0 | |
Protectio Thermalis | Ita | |
Status Operandi/Indicatio Culpae | Viridis bene/Ruber vitium | |
Contactus Remoti (RC) | Facultativum | |
Capacitas Commutationis RC | AC: 250V / 0.5A; ABC: 250V / 0.1A; 125V / 0.2A; 75V / 0.5A | |
Sectio Transversa Conductoris RC (max) | 16AWG (Solidum)/1.5mm²(Venditum) |
Informationes Ordinis
Ordo Codex | 75 | CL | 275 | 320 |
BY1-12.5-XXX/1+1 | 1207513 | 1215013 | 1227513 | 1232013 |
BY1-12.5-XXX/1S+1 (cumcontactus remoti) | 1207514 | 1215014 | 1227514 | 1232014 |
BY1-12.5-XXX/0 (moduli reservati) | 1207501 | 1215001 | 1227501 | 1232001 |
BY1-12.5-NPE/0 (moduli reservati) | 1205501 | 1255001 | 1225501 | 1225501 |
Legenda
Linea L
N Neutralis
Terra Protectoria PE
Contactus Signationis S (Optionales)
BY1-XII.5-XXX/1(S)+1 | CL | 275 | 320 | 385 |
Dimensiones Unitatis Singulae DIN 43880 | 1 CTN | |||
Dimensiones Involucri (A × L × L) | [200×230×330mm] | |||
Quantitas Minima Ordinis | 32Unitates |
BY1-XII.5-XXX/0 | CL | 275 | 320 | 385 |
BY1-12.5-NPE/0 | 25 | |||
Dimensiones Unitatis Singulae DIN 43880 | 1 CTN | |||
Dimensiones Involucri (A × L × L) | [200×230×330mm] | |||
Quantitas Minima Ordinis | 64Unitates |